Parameters
List of Parameters
p1023[0...n]
BI: Fixed speed setpoint selection Bit 3 / n_set_fixed Bit 3
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1020, p1021, p1022, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1024
CO: Fixed speed setpoint effective / n_set_fixed eff
Access level: 3
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the selected and effective fixed speed setpoint.
This setpoint is the output value for the fixed speed setpoints and must be appropriately interconnected (e.g. with
the main setpoint).
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1070, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1025.0
BO: Fixed speed setpoint status / n_setp_fix status
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status when selecting the fixed speed setpoints.
Bit field:
Bit
Signal name
00
Fixed speed setpoint selected
Dependency:
Refer to: p1016
Note:
Re bit 00:
When the fixed speed setpoints are directly selected (p1016 = 1), this bit is set if at least 1 fixed speed setpoint is
selected.
1-138
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
Data type: Unsigned8
Data set: -
Factory setting
-
0 signal
No
© Siemens AG 2011 All Rights Reserved