Siemens CU240B-2 Parameter Manual page 373

Table of Contents

Advertisement

r9776
SI diagnostics / SI diagnostics
CU240E-2
Access level: 4
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
-
Description:
The parameter is used for diagnostics.
Bit field:
Bit
Signal name
00
Safety parameter changed POWER ON
required
Note:
Re bit 00 = 1:
At least one Safety parameter has been changed that will only take effect after a POWER ON.
r9780
SI monitoring clock cycle (processor 1) / SI mon_clk cyc P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
- [ms]
Description:
Displays the clock cycle time for the Safety Integrated Basic Functions on processor 1.
r9781[0...1]
SI checksum to check changes (processor 1) / SI chg chksm P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
-
Description:
Displays the checksum for tracking changes for Safety Integrated.
These are additional checksums that are created to track changes (fingerprint for the "safety logbook" functionality)
to safety parameters (that are relevant for checksums).
Index:
[0] = SI checksum to track functional changes
[1] = SI checksum to track hardware-specific changes
Dependency:
Refer to: p9601, p9729, p9799
Refer to: F01690
r9782[0...1]
SI time stamp to check changes (processor 1) / SI chg t P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
- [h]
Description:
Displays the time stamps for the checksums for tracking changes for Safety Integrated.
The time stamps for the checksums for tracking changes (fingerprint for the "safety logbook" functionality) made to
safety parameters are saved in parameters p9781[0] and p9781[1].
Index:
[0] = SI time stamp for checksum to track functional changes
[1] = SI time stamp for checksum to track hardware-specific changes
Dependency:
Refer to: p9601, p9729, p9799
Refer to: F01690
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [h]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
Data type: FloatingPoint32
Data set: -
Factory setting
- [ms]
Data type: Unsigned32
Data set: -
Factory setting
-
Data type: FloatingPoint32
Data set: -
Factory setting