p2257
Technology controller, ramp-up time / Tec_ctrl t_ramp-up
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the ramp-up time of the technology controller.
Dependency:
Refer to: p2258
Note:
The ramp-up time is referred to 100 %.
p2258
Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the ramp-down time of the technology controller.
Dependency:
Refer to: p2257
Note:
The ramp-down time is referred to 100 %.
r2260
CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
Access level: 2
Can be changed: -
Units group: 9_1
Min
- [%]
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
p2261
Technology controller setpoint filter time constant / Tec_ctrl set T
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the time constant for the setpoint filter (PT1) of the technology controller.
r2262
CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
Access level: 4
Can be changed: -
Units group: 9_1
Min
- [%]
Description:
Displays the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: FloatingPoint32
Data set: -
Factory setting
0.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]