Siemens CU240B-2 Parameter Manual page 288

Table of Contents

Advertisement

Parameters
List of Parameters
p2161[0...n]
Speed threshold 3 / n_thresh val 3
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency:
Refer to: p2150, r2199
p2162[0...n]
Hysteresis speed n_act > n_max / Hyst n_act>n_max
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Dependency:
Refer to: r1084, r1087, r2197
Notice:
For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p2162 <= 1.02 * p0322 - p1082
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commission-
ing mode.
Note:
For a negative speed limit (r1087) the hysteresis is effective below the limit value and for a positive speed limit
(r1084) above the limit value.
If significant overshoot occurs in the maximum speed range (e.g. due to load shedding), you are advised to
increase the dynamic response of the speed controller (if possible). If this is insufficient, the hysteresis p2162 can
only be increased by more than 10% of the rated speed when the maximum speed (p0322) of the motor is suffi-
ciently greater than the speed limit p1082.
p2163[0...n]
Speed threshold 4 / n_thresh val 4
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
p2164[0...n]
Hysteresis speed 4 / n_hysteresis 4
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" signal/mes-
sage (BO: r2197.7).
Dependency:
Refer to: p2163, p2166, r2197
1-288
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
60000.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
200.00 [rpm]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
5.00 [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
90.00 [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
2.00 [rpm]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents