Siemens CU240B-2 Parameter Manual page 214

Table of Contents

Advertisement

Parameters
List of Parameters
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3
Can be changed: -
Units group: 7_1
Min
- [Nm]
Description:
Displays the lower torque limit of all torque limits without offset.
Dependency:
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1530[0...n]
Power limit motoring / P_max mot
Access level: 2
Can be changed: U, T
Units group: 14_5
Min
0.00 [kW]
Description:
Sets the power limit when motoring.
Dependency:
Refer to: p0500, p1531
Note:
The power limit is limited to 300% of the rated motor power.
1-214
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
100000.00 [kW]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [Nm]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1524[0]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1525[0]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [kW]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents