Siemens CU240B-2 Parameter Manual page 720

Table of Contents

Advertisement

Faults and Alarms
List of Faults and Alarms
F30081
Power unit: Switching operations too frequent
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has executed too many switching operations for current limitation.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
F30105
PU: Actual value sensing fault
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one incorrect actual value channel was detected on the Power Stack Adapter (PSA).
The incorrect actual value channels are displayed in the following diagnostic parameters.
Remedy:
Evaluate the diagnostic parameters.
If the actual value channel is incorrect, check the components and if required, replace.
A30502
Power unit: DC link overvoltage
Reaction:
NONE
Acknowledge:
NONE
Cause:
The power unit has detected overvoltage in the DC link on a pulse inhibit.
- device connection voltage too high.
- line reactor incorrectly dimensioned.
Fault value (r0949, decimal interpretation):
DC link voltage [1 bit = 100 mV].
See also: r0070 (Actual DC link voltage)
Remedy:
- check the device supply voltage (p0210).
- check the dimensioning of the line reactor.
See also: p0210 (Drive unit line supply voltage)
F30600
SI P2: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A.
- forced checking procedure of the safety shutdown path via processor 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, decimal interpretation):
0: Stop request from processor 1.
1005: Pulses suppressed although STO not selected and there is no internal STOP A present.
1010: Pulses enabled although STO is selected or an internal STOP A is present.
9999: Subsequent response to fault F30611.
Remedy:
Select Safe Torque Off and de-select again.
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
STO: Safe Torque Off
3-720
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
© Siemens AG 2011 All Rights Reserved