Faults and Alarms
List of Faults and Alarms
F03505 (N, A)
CU: Analog input wire breakage
Reaction:
OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The input current of the analog input has undershot the threshold value parameterized in p0761[0...3].
This fault only occurs when p0756[0...1] = 1 (2 ... 10 V with monitoring) or p0756[0...2] = 3 (4 ... 20 mA with
monitoring) is set.
p0756[0]: Analog input 0
p0756[1]: Analog input 1
p0756[2]: Analog input 2
Fault value (r0949, decimal interpretation):
The component number (p0151) of the component involved is specified at the units, tens and hundreds digit.
The thousands digit specifies the relevant analog input: 0: analog input 0 (AI 0), 1: analog input 1 (AI 1), 2: analog
input 2 (AI 2)
Remedy:
Check the connection to the signal source for interruptions.
Check the magnitude of the injected current - it is possible that the infed signal is too low.
The input current measured by the analog input can be read in r0752[x].
A03510 (F, N)
CU: Calibration data not plausible
Reaction:
NONE
Acknowledge:
NONE
Cause:
During booting, the calibration data for the analog inputs is read and checked with respect to plausibility.
At least one calibration data point was determined to be invalid.
Remedy:
- power down/power up the power supply for the Control Unit.
If it reoccurs, replace the module.
In principle, operation could continue.
The analog channel involved possibly does not achieve the specified accuracy.
A05000 (N)
Power unit: Overtemperature heat sink AC inverter
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for overtemperature at the inverter heat sink has been reached. The response is set using
p0290.
If the temperature of the heat sink increases by an additional 5 K, then fault F30004 is initiated.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- have the load conditions and the load duty cycle been appropriately dimensioned?
- has the cooling failed?
A05001 (N)
Power unit: Overtemperature depletion layer chip
Reaction:
NONE
Acknowledge:
NONE
Cause:
Alarm threshold for overtemperature of the power semiconductor in the AC converter has been reached.
Note:
- The response is set using p0290.
- If the depletion layer temperature increases by an additional 15 K, then fault F30025 is triggered.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- have the load conditions and the load duty cycle been appropriately dimensioned?
- has the cooling failed?
- pulse frequency too high?
See also: r0037 (Power unit temperatures), p0290 (Power unit overload response)
3-688
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011