Siemens CU240B-2 Parameter Manual page 298

Table of Contents

Advertisement

Parameters
List of Parameters
p2200[0...n]
BI: Technology controller enable / Tec_ctrl enable
Access level: 2
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
p2201[0...n]
CO: Technology controller, fixed value 1 / Tec_ctr fix val 1
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2202[0...n]
CO: Technology controller, fixed value 2 / Tec_ctr fix val 2
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2203[0...n]
CO: Technology controller, fixed value 3 / Tec_ctr fix val 3
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the value for fixed value 3 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2204[0...n]
CO: Technology controller, fixed value 4 / Tec_ctr fix val 4
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the value for fixed value 4 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
1-298
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
10.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
20.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
30.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
40.00 [%]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents