Siemens CU240B-2 Parameter Manual page 374

Table of Contents

Advertisement

Parameters
List of Parameters
r9794[0...19]
SI crosswise comparison list (processor 1) / SI CDC_list P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
-
Description:
Displays the numbers of the data items that are currently being compared crosswise on processor 1.
The content of the list of crosswise-compared data is dependent upon the particular application.
Note:
Example:
r9794[0] = 1 (monitoring clock cycle)
r9794[1] = 2 (enable safety functions)
r9794[2] = 3 (F-DI changeover, tolerance time)
...
A complete list of numbers for crosswise-compared data items appears in fault F01611.
r9795
SI diagnostics STOP F (processor 1) / SI diag STOP F P1
CU240E-2
Access level: 2
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
-
Description:
Displays the number of the cross-checked data item which caused STOP F on processor 1.
Dependency:
Refer to: F01611
Note:
A complete list of numbers for crosswise-compared data items appears in fault F01611.
r9798
SI actual checksum SI parameters (processor 1) / SI act chksm P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: -
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
-
Description:
Displays the checksum for the Safety Integrated parameters checked using checksums on processor 1 (actual
checksum).
Dependency:
Refer to: p9799, r9898
p9799
SI setpoint checksum SI parameters (processor 1) / SI setp_chksm P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: C(95)
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
0000 hex
Description:
Sets the checksum for the Safety Integrated parameters checked using checksums on processor 1 (setpoint check-
sum).
Dependency:
Refer to: r9798, p9899
1-374
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
FFFF FFFF hex
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
0000 hex
© Siemens AG 2011 All Rights Reserved