Siemens CU240B-2 Parameter Manual page 392

Table of Contents

Advertisement

Parameters
List of Parameters
r10149
SI F-DI monitoring status (processor 2) / SI F-DI status P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: -
Units group: -
Min
-
Description:
Displays the monitoring status of the fail-safe digital inputs (F-DI).
The F-DIs that are being used by the Safety Integrated functions are displayed.
If the module used has fewer than 3 F-DIs, "Freely available" is displayed for the F-DIs which are not in use.
Bit field:
Bit
Signal name
00
F-DI 0
01
F-DI 1
02
F-DI 2
Dependency:
p10006 / p10106
p10022 / p10122
p10023 / p10123
p10026 / p10126
p10030 / p10130
p10031 / p10131
p10050 / p10150
Refer to: r10049
p10150
SI PROFIsafe F-DI transfer (processor 2) / SI Ps F-DI tran P2
CU240E-2 DP F
Access level: 3
Can be changed: C(95)
Units group: -
Min
-
Description:
Setting for the transfer and evaluation of failsafe digital inputs (F-DI) via PROFIsafe.
The safe state of the selected F-DIs is transferred to the F-control via PROFIsafe. The F-DIs are monitored for dis-
crepancies. Discrepancy faults can be acknowledged via PROFIsafe.
Bit field:
Bit
Signal name
00
F-DI 0
01
F-DI 1
02
F-DI 2
Dependency:
Refer to: p10050
Note:
F-DI: Failsafe Digital Input
1-392
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Safety monitored
Safety monitored
Safety monitored
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Transfer
Transfer
Transfer
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
Freely available
Freely available
Freely available
Data type: Unsigned32
Data set: -
Factory setting
0000 bin
0 signal
No transfer
No transfer
No transfer
© Siemens AG 2011 All Rights Reserved
FP
-
-
-
FP
-
-
-