Siemens CU240B-2 Parameter Manual page 115

Table of Contents

Advertisement

p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_src 1
CU240B-2 DP
Access level: 3
CU240E-2 DP
Can be changed: T
CU240E-2 DP F
Units group: -
Min
-
Description:
Sets the first signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switch on inhibit)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- No OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0845[0...n]
BI: No coast-down / coast-down (OFF2) signal source 2 / OFF2 S_src 2
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the second signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switch on inhibit)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- No OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
[0] 2090.1
[1] 1
[2] 2090.1
[3] 2090.1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
1-115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents