Parameters
List of Parameters
p0757[0...1]
CU analog inputs characteristic value x1 / CU AI char x1
Access level: 2
Can be changed: U, T
Units group: -
Min
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
p0758[0...1]
CU analog inputs characteristic value y1 / CU AI char y1
Access level: 2
Can be changed: U, T
Units group: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
p0759[0...1]
CU analog inputs characteristic value x2 / CU AI char x2
Access level: 2
Can be changed: U, T
Units group: -
Min
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
p0760[0...1]
CU analog inputs characteristic value y2 / CU AI char y2
Access level: 2
Can be changed: U, T
Units group: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
1-98
Calculated: -
Scaling: -
Unit selection: -
Max
160.000
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
160.000
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
0.000
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
10.000
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
© Siemens AG 2011 All Rights Reserved