Siemens CU240B-2 Parameter Manual page 31

Table of Contents

Advertisement

r0052.0...15
CO/BO: Status word 1 / ZSW 1
Access level: 2
Can be changed: -
Units group: -
Min
-
Description:
Displays status word 1.
Bit field:
Bit
Signal name
00
Rdy for switch on
01
Ready
02
Operation enabled
03
Fault present
04
Coast down active (OFF2)
05
Quick Stop active (OFF3)
06
Switching on inhibited active
07
Alarm present
08
Deviation, setpoint/actual speed
09
Control request
10
Maximum speed reached
11
I, M, P limit reached
12
Motor holding brake open
13
Alarm motor overtemperature
14
Motor rotates forwards
15
Alarm drive converter overload
Caution:
p2080 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
The following status bits are displayed in r0052.
Bit 00: r0899 Bit 0
Bit 01: r0899 Bit 1
Bit 02: r0899 Bit 2
Bit 03: r2139 Bit 3 (or r1214 Bit 10, if p1210 > 0)
Bit 04: r0899 Bit 4
Bit 05: r0899 Bit 5
Bit 06: r0899 Bit 6
Bit 07: r2139 Bit 7
Bit 08: r2197 Bit 7
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 12: r0899 Bit 12
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
No
Yes
No
Yes
No
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
No
No
No
Yes
Yes
No
No
Yes
No
No
Yes
No
Yes
No
Yes
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents