Siemens CU240B-2 Parameter Manual page 709

Table of Contents

Advertisement

F08702 (A)
CAN: RPDO Timeout
Reaction:
OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time of the CANopen RPDO telegram has expired because the bus connection was either interrupted
or the CANopen Master was switched-off.
Remedy:
- check the bus cable
- check the master.
- If required, increase the monitoring time (p8699).
A08751
CAN: Telegram loss
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CAN controller has lost a receive message (telegram).
Remedy:
Reduce the cycle times of the receive messages.
A08752
CAN: Error counter for error passive exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The error counter for the send or receive telegrams has exceeded the value 127.
Remedy:
- check the bus cable
- set a higher baud rate (p8622).
- check the bit timing and if required optimize (p8623).
A08753
CAN: Message buffer overflow
Reaction:
NONE
Acknowledge:
NONE
Cause:
A message buffer overflow.
Alarm value (r2124, interpret decimal):
1: Non-cyclic send buffer (SDO response buffer) overflow.
2: Non-cyclic receive buffer (SDO receive buffer) overflow.
3: Cyclic send buffer (PDO send buffer) overflow.
Remedy:
- check the bus cable.
- set a higher baud rate (p8622).
- check the bit timing and if required optimize (p8623).
Re alarm value = 2:
- reduce the cycle times of the SDO receive messages.
- SDO request from master only after SDO feedback for previous SDO request.
A08754
CAN: Incorrect communications mode
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the "operational" mode, an attempt was made to change parameters p8700 ... p8737.
Remedy:
Change to the "pre-operational" or "stopped" mode.
A08755
CAN: Obj cannot be mapped
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CANopen object is not provided for the Process Data Object (PDO) Mapping.
Remedy:
Use a CANopen object intended for the PDO mapping or enter 0.
The following objects can be mapped in the Receive Process Data Object (RPDO) or Transmit Process Data Object
(TPDO):
- RPDO: 6040 hex, 6060 hex, 60FF hex, 6071 hex; 5800 hex - 580F hex; 5820 hex - 5827 hex
- TPDO: 6041 hex, 6061 hex, 6063 hex, 6069 hex, 606B hex, 606C hex, 6074 hex; 5810 hex - 581F hex; 5830 hex
- 5837 hex
Only sub-index 0 of the specified objects can be mapped.
Note:
As long as A08755 is present, the COB-ID cannot be set to valid.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Faults and Alarms
List of Faults and Alarms
3-709

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents