p1570[0...n]
CO: Flux setpoint / Flux setpoint
Access level: 3
Can be changed: U, T
Units group: -
Min
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
p1571[0...n]
CI: Supplementary flux setpoint / Suppl flux setp
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the supplementary flux setpoint.
Notice:
Low flux setpoints can cause the drive to stall at higher loads. This is the reason that the flux setpoint should only be
adapted for slow load changes.
Note:
The supplementary flux setpoint is limited to +/- 50 %.
p1573[0...n]
Flux threshold value magnetizing / Flux thresh magnet
Access level: 3
Can be changed: U, T
Units group: -
Min
10.0 [%]
Description:
Sets the flux threshold value for enabling the speed setpoint and the end of magnetizing (r0056.4).
Note:
The parameter only has an influence if the flux actual value reaches the threshold value p1573 more quickly during
magnetizing than the time set in p0346.
The parameter has no influence for flying restart (see p1200) and after DC braking (see p1231).
p1574[0...n]
Voltage reserve dynamic / U_reserve dyn
PM230
Access level: 3
Can be changed: U, T
Units group: 5_1
Min
0.0 [Vrms]
Description:
Sets a dynamic voltage reserve.
Dependency:
Refer to: p0500
Note:
In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due
to the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage
reserve. Increasing the reserve reduces the steady-state maximum output voltage (r0071).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.0 [%]
Calculated: -
Scaling: p2003
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.0 [%]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
150.0 [Vrms]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.0 [%]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.0 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
2.0 [Vrms]
1-217