p3111[0...n]
BI: External fault 3, enable / Ext fault 3 enab
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3112
Refer to: F07862
p3112[0...n]
BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Refer to: F07862
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status of NAMUR signal bit bar.
The faults or alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Bit field:
Bit
Signal name
00
Fault drive converter data electronics / soft-
ware error
01
Line supply fault
02
DC link overvoltage
03
Fault drive converter power electronics
04
Drive converter overtemperature
05
Ground fault
06
Motor overload
07
Bus error
08
External safety-relevant shutdown
10
Error communication internal
11
Fault infeed
15
Other faults
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
-
-
-
-