Siemens CU240B-2 Parameter Manual page 127

Table of Contents

Advertisement

p0971
Save parameters / Save par
Access level: 1
Can be changed: U, T
Units group: -
Min
0
Description:
Setting to save parameters in the non-volatile memory.
Value:
0:
1:
10:
11:
12:
Dependency:
Refer to: p1960, r3996
Caution:
If a memory card (optional) is inserted, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
Caution:
The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Notice:
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
p0972
Drive unit reset / Drv_unit reset
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the required procedure to execute a hardware reset for the drive unit.
Value:
0:
1:
2:
3:
Danger:
It must be absolutely ensured that the system is in a safe condition.
The memory card/device memory of the Control Unit must not be accessed.
Note:
If value = 1:
Reset is immediately executed and communications interrupted.
After communications have been established, check the reset operation (refer below).
If value = 2:
Help to check the reset operation.
Firstly, set p0972 = 2 and then read back. Secondly, set p0972 = 1 (it is possible that this request is possibly no lon-
ger acknowledged). The communication is then interrupted.
After communications have been established, check the reset operation (refer below).
If value = 3:
The reset is executed after interrupting cyclic communication. This setting is used to implement a synchronized
reset by a control for several drive units.
If the cyclic communication is active for both PROFIdrive interfaces, then the reset is executed after completing
both cycle communications.
After communications have been established, check the reset operation (refer below).
To check the reset operation:
After the drive unit has been restarted and communications have been established, read p0972 and check the fol-
lowing:
p0972 = 0? --> The reset was successfully executed.
p0972 > 0? --> The reset was not executed.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Inactive
Save drive object
Save in non-volatile memory as setting 10
Save in non-volatile memory as setting 11
Save in non-volatile memory as setting 12
Inactive
Hardware-Reset immediate
Hardware reset preparation
Hardware reset after cyclic communication has failed
Calculated: -
Scaling: -
Unit selection: -
Max
12
Calculated: -
Scaling: -
Unit selection: -
Max
3
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Unsigned16
Data set: -
Factory setting
0
1-127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f