Pinouts For The Jcs 1200 Alarm Panel Interface Connector; Table 37: Pinouts For The Alarm Panel Interface Connector - Juniper JCS 1200 Hardware Manual

Juniper control system platform
Hide thumbs Also See for JCS 1200:
Table of Contents

Advertisement

Pinouts for the JCS 1200 Alarm Panel Interface Connector

The alarm panel module provides one DB-15 connector (male) for critical, major,
and minor telco alarms. Each of the alarms has a relay that enables multiple system
alarm indicators to be daisy-chained together. Table 37 on page 213 shows the pinouts
for the alarm panel interface connector.

Table 37: Pinouts for the Alarm Panel Interface Connector

Related Topics
Pin #
Description
1
Minor alarm reset +
2
Minor alarm reset –
3
Major alarm reset +
4
Major alarm reset –
5
Critical alarm normally open
6
Critical alarm normally closed
7
Critical alarm common
8
Minor alarm normally open
9
Minor alarm normally closed
10
Minor alarm common
11
Major alarm normally open
12
Major alarm normally closed
13
Major alarm common
14
Reserved
15
Reserved
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12