Appendix B
Environmental Specifications
JCS 1200 Platform Environmental Specifications
JCS 1200 Platform Environmental Specifications on page 187
Table 25 on page 187 specifies the environmental specifications required for normal
platform operation. In addition, the site should be as dust-free as possible. Dust can
clog air intake vents, reducing cooling system efficiency. Check the vents frequently,
cleaning them as necessary.
Table 25: Platform Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic activity
Maximum thermal output
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to
85%, noncondensing
Normal operation ensured in temperature range of 41° F (5° C) to
104° F (40° C)
Nonoperating storage temperature in shipping crate:
–40° F (–40° C) to 158° F (70° C)
Tested to meet Telcordia Technologies Zone 4 earthquake
requirements
DC power: 10,742 BTU/hour (3150 W)
AC power: 11,935 BTU/hour (3500 W)
NOTE: These specifications are estimates and subject to change.