Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE: The actual wire gauge and ring terminal are determined by the current draw
and the length of wire run or as specified by the customer premises guidelines.
Related Topics
DC Power Disconnection Warning for the JCS 1200 Platform
WARNING: Before performing any of the following procedures, ensure that power
is removed from the DC circuit. To ensure that all power is off, locate the circuit
breaker on the panel board that services the DC circuit, switch the circuit breaker to
the
Waarschuwing Voordat u een van de onderstaande procedures uitvoert, dient u te
controleren of de stroom naar het gelijkstroom circuit uitgeschakeld is. Om u ervan
te verzekeren dat alle stroom UIT is geschakeld, kiest u op het schakelbord de
stroomverbreker die het gelijkstroom circuit bedient, draait de stroomverbreker naar
de UIT positie en plakt de schakelaarhendel van de stroomverbreker met plakband
in de UIT positie vast.
Varoitus Varmista, että tasavirtapiirissä ei ole virtaa ennen seuraavien toimenpiteiden
suorittamista. Varmistaaksesi, että virta on KATKAISTU täysin, paikanna tasavirrasta
huolehtivassa kojetaulussa sijaitseva suojakytkin, käännä suojakytkin
KATKAISTU-asentoon ja teippaa suojakytkimen varsi niin, että se pysyy
KATKAISTU-asennossa.
176
DC Power Disconnection Warning for the JCS 1200 Platform
The JCS 1200 platform requires a DC wire rating of 4 AWG (circular mil area of
33100-52600) and of 90° C.
Flexible DC wiring is recommended to allow for minimum bend radius.
The supply wiring to the power connectors must be terminated in UL-recognized
insulated ring terminals, sized for an M6 stud, 4 AWG wire (circular mil area of
33100-52600), and a wire insulation diameter of 12.8 to 13.1 mm. An example
of this type of ring terminal is Amp Plasti-Grip type 520431 using Tyco Electronics
Hydraulic Crimping Tool part number 14907491.
For NEBS compliance, the grounding cable must use copper conductors with a
size minimum of 6 AWG (circular mil area of 2080033100) and must be
terminated in a UL-recognized two-hole lug sized for an M6 stud. An example
of this type of two-hole lug is the Thomas and Betts part number 54205 using
the Thomas and Betts crimping tool model TBM-25S.
Torque the wiring-terminal nuts to 13.3 lb-in. (1.5 Nm)
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
OFF
position, and tape the switch handle of the circuit breaker in the
OFF
position.