Green and yellow—Earth
Blue—Neutral
Brown—Live
The power cable warning in Japanese is as follows:
WARNING: The attached power cable is only for this product. Do not use the cable
for another product.
Connecting the JCS 1200 AC Platform to AC Power on page 62
Related Topics
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190

JCS 1200 DC Power Electrical Safety Guidelines and Warnings

When working with DC-powered equipment, observe the following guidelines and
warnings:
JCS 1200 DC Power Electrical Safety Guidelines on page 175
DC Power Disconnection Warning for the JCS 1200 Platform on page 176
JCS 1200 DC Power Grounding Requirements and Warning on page 178
DC Power Wiring Sequence Warning for the JCS 1200 Platform on page 179
DC Power Wiring Terminations Warning for the JCS 1200 Platform on page 180
JCS 1200 DC Power Electrical Safety Guidelines
The following guidelines are provided for connecting a 60-A JCS 1200 platform to a
–48 V DC power source:
The power source must have a minimum of 80 A overcurrent protection. See
article 240, paragraph 3, table 310-16 of the National Electric Code for more
information about electrical wiring requirements.
The overcurrent protective device or circuit breaker must be accessible to service
personnel to prevent the power from being turned on by someone other than a
technician servicing the JCS 1200 platform.