EN50131-3 Compliancy
In order to be compliant with the technical specification EN50131-3 (Alarm
systems – Control and indicating equipment), the following guidelines must be
taken into account:
•
The tamper of the warning device should be connected to a 24 hour zone
input.
•
Overriding is not supported with xGen. In case a zone is faulted, one shall
bypass the zone manually before arming or verify the zone and clear the fault.
See user instructions
•
Hold-up zones are not allowed to be set for bypass
•
Zone isolation is not supported
Options affected by EN 50131 regulations
EN 50131 Grade 2 Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
•
Period, 24 h for every path to meet ATS Class 2, 4 h for the IP path to meet
Class 4.
•
View Partitions and 2.2.1.n.3.4 Control Partitions settings are identical
•
Buzzer silent, never
•
Quick set, off
•
Function keys, all set to None
•
User group options, 25. No OP/CL reports option set to No
•
Inhibit, set to No for all zones with type 5. Panic, 6. 24H
•
Swinger shunt, set to Yes for all zones
•
ACK on keypad, set to None for all zones with type 9. Keyswitch
•
Entry time, 45 s maximum
•
Entry alarms, Instant
•
Active, set to No for all schedules.
•
Activation, internal and external siren 90 to 900 s
•
Delay time, external siren 600 s maximum
•
Armed display, 30 s maximum
•
Mains reporting delay, 3600 s maximum
•
User code required, enabled
•
Armed display, always
•
Alarm list, disabled