Figure 126: Attaching the Power Cord to the High Capacity Delta AC PDU

Connect the wires to the AC terminal block on the High Capacity Delta AC PDU
7.
(Figure 127 on page
228). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of
the input terminal screws and the grounding point screw, insert each wire into the
grounding point or input terminal, and tighten the screw.
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Figure 127: Connecting Ground and Power to a High Capacity Delta AC
PDU
into the grounding point.
GND
into the
input terminal.
L1
L1
into the
input terminal.
L2
L2
into the
input terminal.
L3
L3
Copyright © 2017, Juniper Networks, Inc.