PTX5000 Packet Transport Router Hardware Guide
312
Disconnect the wires from the AC terminal block on the three-phase delta AC power
8.
supply
(Figure 187 on page
the input terminal or grounding point screw, and remove each wire from the input
terminal or grounding point.
Remove the wire labeled
a.
Remove the wire labeled
b.
Remove the wire labeled
c.
Remove the wire labeled
d.
Figure 187: Disconnecting AC Power Wires from a Three-Phase Delta AC
Power Supply
Using a number 2 Phillips (+) screwdriver, loosen the captive screws that secure the
9.
metal retaining bracket and AC power cord to the PDU. While gently removing the
wires of the AC power cord from the wiring compartment, remove the metal retaining
bracket and AC power cord from the PDU. See
312). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen
L3
from the
L3
input terminal.
L2
from the
L2
input terminal.
L1
from the
L1
input terminal.
GND
from the grounding point.
Figure 188 on page
Copyright © 2017, Juniper Networks, Inc.
313.