Using a number 2 Phillips (+) screwdriver, loosen the two captive screws to the metal
7.
wiring compartment door. Open the door of the metal wiring compartment. Disconnect
the wires from the AC terminal block on the three-phase wye AC PDU
(Figure 201 on page
327). Using 1/5-in. (5.5-mm) slotted screw, loosen the input terminal
or grounding point screw, and remove each wire from the input terminal or grounding
point.
Remove the wire labeled
a.
Remove the wire labeled
b.
Remove the wire labeled
c.
Remove the wire labeled
d.
Figure 201: Disconnecting AC Power Wires from a Three-Phase Wye AC
PDU
Using a number 2 Phillips (+) screwdriver, loosen the screws that secure the metal
8.
retaining bracket and AC power cord to the PDU. While gently removing the wires of
the AC power cord from the wiring compartment, remove the metal retaining bracket
and AC power cord from the PDU. See
Chapter 27: Removing and Installing Power System Components
L3
from the
L3
input terminal.
L2
from the
L2
input terminal.
L1
from the
L1
input terminal.
GND
into the grounding point.
Figure 202 on page
328.
327