Open the door of the metal wiring compartment. Disconnect the wires from the AC
6.
terminal block on the three-phase delta AC power supply
Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen the input terminal or grounding
point screw, and remove each wire from the input terminal or grounding point.
Remove the wire labeled
a.
Remove the wire labeled
b.
Remove the wire labeled
c.
Remove the wire labeled
d.

Figure 194: Disconnecting AC Power Wires from a Three-Phase Delta AC

PDU
Using a number 2 Phillips (+) screwdriver, loosen the captive screws that secure the
7.
metal retaining bracket and AC power cord to the PDU. While gently removing the
wires of the AC power cord from the wiring compartment, remove the metal retaining
bracket and AC power cord from the PDU. See
Chapter 27: Removing and Installing Power System Components
L3
from the
L3
input terminal.
L2
from the
L2
input terminal.
L1
from the
L1
input terminal.
GND
into the grounding point.
Figure 195 on page
(Figure 194 on page
321).