Table 60: Ac Power Cord Specifications For The Three-Phase Ac Power - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

Table 60: AC Power Cord Specifications for the Three-Phase AC Power Cords
Power
Cord
Region
Model Number
Delta
North
CBL-PTX-AC-D
America
CBL2-PTX-100AC-D
CBL2-PTX-150AC-D
Wye
Europe
CBL-PTX-AC-W
CBL2-PTX-AC-W-S
Copyright © 2017, Juniper Networks, Inc.
NOTE:
In North America, AC power cords must not exceed 4.5 m
(approximately 14.8 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3). The cords supplied with the router are in
compliance.
Each AC PDU has a metal wiring compartment that contains the AC terminal block and
ground.
The delta AC terminal block consists of three input terminals labeled
from left to right.
The wye AC terminal block consists of four input terminals labeled
from left to right.
Table 60 on page 133
provides specifications for the AC power cords.
Electrical Specification
60 A @ 250 VAC
100 A @ 250 V
150 A @ 250 A
32 A @ 400 VAC
63 A @ 400 VAC
Figure 66 on page 134
and
each region supported.
Chapter 10: AC Power Specifications and Requirements
Figure 67 on page 134
show the AC power cord provided for
L1
,
L2
, and
,
,
, and
L1
L2
L3
Plug Type
Wire
IEC60309
4 wires labeled
,
,
,
GND
L1
L2
and
L3
IEC60309
5 wires labeled
GND
,
L1
,
L2
,
L3
,
and
N
L3
,
,
N
Pole
3-pole
4-pole
133