CHAPTER 10
AC Power Specifications and
Requirements
PTX5000 AC Power System Specifications
Copyright © 2017, Juniper Networks, Inc.
PTX5000 AC Power System Specifications on page 129
PTX5000 Three-Phase Delta AC Power Distribution Unit Specifications on page 130
PTX5000 Three-Phase Wye AC Power Distribution Unit Specifications on page 130
PTX5000 High Capacity Delta AC Power Distribution Unit Specifications on page 131
PTX5000 High Capacity Wye AC Power Distribution Unit Specifications on page 131
PTX5000 High Capacity Single-Phase AC Power Distribution Unit
Specifications on page 132
PTX5000 AC Power Cord Specifications on page 132
Table 54 on page 129
lists the AC power system electrical specifications.
Table 54: AC Power System Electrical Specifications
Item
AC input voltage
AC input line frequency
AC system current rating
AC system input power
Specification
Delta operating range: 200 through 240 VAC (line-to-line)
(nominal)
Wye operating range:
200 through 240 VAC (line-to-neutral) (nominal)
346 through 415 VAC (line-to-line) (nominal)
Delta: 50/60 Hz (nominal)
Wye: 50/60 Hz (nominal)
Delta: 48 A @ 200 VAC (line-to-neutral)
Wye: 30 A @ 346 VAC (line-to-line)
Delta: 17,600 W
Wye: 17,600 W
129