PTX5000 Packet Transport Router Hardware Guide
358
Connect the wires to the AC terminal block on the High Capacity Wye AC PDU
10.
(Figure 230 on page
358). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen the
input terminal screws and the grounding point screw, and insert each wire into the
grounding point or input terminal, and tighten the screw.
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Insert the wire labeled
e.
Figure 230: Connecting Grounding and AC Power Wires to a High Capacity
Wye AC PDU
Verify that the AC power and grounding wire connections are correct.
11.
Using a number 2 Phillips (+) screwdriver, tighten the two captive screws on the metal
12.
AC wiring compartment.
Verify that the AC power cord is does not touch or block access to chassis components,
13.
and that it does not drape where people could trip on it.
GND
into the grounding point.
L1
into the
L1
input terminal.
L2
into the
L2
input terminal.
L3
into the
L3
input terminal.
N
into the
N
input terminal.
Copyright © 2017, Juniper Networks, Inc.