Ac Pdus Supported On The Ptx5000; Ptx5000 Normal Capacity Delta And Wye Ac Pdus; Normal Capacity Three-Phase Delta Ac Pdu Components; Table 16: Ac Pdus Supported On The Ptx5000 - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

AC PDUs Supported on the PTX5000

PTX5000 Normal Capacity Delta and Wye AC PDUs

Copyright © 2017, Juniper Networks, Inc.
The PTX5000 supports the AC PDUs in
NOTE:
Ensure that you use AC PDUs of the same model number during normal
operation.

Table 16: AC PDUs Supported on the PTX5000

Name
Delta AC PDU
Wye AC PDU
High Capacity Delta AC PDU
High Capacity Wye AC PDU
High Capacity Single-Phase AC
PDU
Normal Capacity Three-Phase Delta AC PDU Components on page 43
Normal Capacity Three-Phase Wye AC PDU Components on page 45

Normal Capacity Three-Phase Delta AC PDU Components

Each normal-capacity three-phase delta AC PDU has the following components (see
Figure 26 on page
44):
A metal retaining bracket located on the lower right to connect the delta AC power
cord to the PDU.
A metal wiring compartment that contains the AC input terminal block and ground.
The AC terminal block consists of three input terminals labeled
One 60-A circuit breaker
A power
switch that provides power to the PSMs.
OUTPUT
LEDs to monitor the status of the PDU.
Twenty-one monitored electronic fuses for the fan trays, Control Boards, and FPCs.
NOTE:
There are no mechanical fuses in the PDU to be replaced. For output
voltage, current protection is provided by electronic fuses, hot-swap circuits,
or ORing circuit. Electronic fuses and hot-swap circuits also provide current
limitation.
Chapter 4: Power System Components and Descriptions
Table 16 on page
43.
Model Number
PDU-PTX-AC-D
PDU-PTX-AC-W
PDU2-PTX-AC-D
PDU2-PTX-AC-W
PDU2-PTX-AC-SP
First Supported Junos
OS Release
12.3
12.3
14.2
14.2
15.1F3, 16.1
L1
,
L2
, and
L3
.
43