PTX5000 Packet Transport Router Hardware Guide
474
NOTE:
After a PDU is powered on, it can take up to 60 seconds for status
indicators—such as the LEDs on the PDU and PSMs, the command output
displays, and messages on the LCD display on the craft interface—to
indicate that the PDU and PSMs are functioning normally. Ignore error
indicators that appear during the first 60 seconds.
Move the
OUTPUT
power switch on the PDU to the on (
10.
Verify that the
11.
PDU OK
LED is off, indicating that the PDU is correctly installed and is functioning properly.
NOTE:
If the
and cabling procedures.
Check the LEDs on the PSMs. For each PSM, verify that the
12.
LEDs are lit steadily green, and that the
NOTE:
If the
FAULT
LED is lit, see
page
535.
On the external management device connected to the Routing Engine, monitor the
13.
startup process to verify that the system has booted properly.
Repeat step 11 through step 14 for the other PDU.
14.
NOTE:
The Routing Engine boots as the PDU completes its startup
sequence.
After powering on a power supply, you must wait at least 60 seconds
before powering it off.
LED on the PDU faceplate is lit steadily and that the
PDU OK
LED does not light steadily, repeat the installation
FAULT
LED is off.
and
LEDs do not light steadily or if the
Input OK
Output OK
"Troubleshooting the PTX5000 Power System" on
|
) position.
FAULT
and
Input OK
Output OK