PTX5000 Packet Transport Router Hardware Guide

Table 23: High Capacity Delta AC PDU LEDs

LED
PDU OK
LED
AC input (
)
~

High Capacity Wye AC PDU

64

Figure 42: High Capacity Delta AC PDU LEDs

1—
PDU OK
LED
Table 23 on page 64
describes the LEDs on the High Capacity Delta AC PDU faceplate.
Color
State
Green
On steadily
Blinking
Red
On steadily
Off
Green
On steadily
Off
Figure 43 on page 65
shows the High Capacity Wye AC PDU LEDs.
2—
AC input (
~
) LED
Description
PDU is functioning normally.
A 36 V converter fault has occurred, but the 36 V output
remains operational.
PDU has failed.
This LED can be off for one of the following reasons:
The PDU is not receiving any input voltage.
The PDU is starting up.
PDU is receiving AC voltage.
Input voltage is not present, or is under –100 VAC.
Copyright © 2017, Juniper Networks, Inc.