EM-1017
Message
Uncommitted WWN change detected. Cold reboot required.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that a user did not commit a changed World Wide Name (WWN) value before performing a
system restart, power cycle, or firmware download operation.
Recommended
Change and commit the new WWN value.
Action
EM-1018
Message
CP blade in slot <slot number> failed to retrieve current chassis type (<return
code>/<error code>/0x<unit number>).
Message Type
FFDC | LOG
Severity
CRITICAL
Probable Cause
Indicates that there was a failure to read the chassis type from the system.
Recommended
Verify that the control processor (CP) blade is operational and is properly seated in its slot.
Action
EM-1019
Message
Current chassis configuration option (<Chassis config option currently in effect>)
is not compatible with standby firmware version (Pre 4.4), cannot allow HA Sync.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that the current chassis configuration option is not supported by the firmware on the standby
control processor (CP). This is true even if the standby CP comes up and is operational. High availability
(HA) synchronization of the CPs will not be allowed.
Recommended
Change the chassis configuration option to 1 using the chassisConfig command, or upgrade the
Action
firmware on the standby CP to the version running on the active CP.