7 Troubleshooting
7.3.11 Troubleshooting the main computer
Continued
6
7
8
9
10
11
12
13
418
Action
Measure the 24V_TRUNK at con-
nector A2.K1.X1.
Make sure that the cables are con-
nected properly at 24V_TRUNK
(A2.K1.X1).
Measure the 24VDC_TRUNK at
connector A1.X6.
Check the UPS LED on the power
distribution board (DSQC1085).
Check error message on FlexPend-
ant and take appropriate action.
Force start the RobotWare Installa-
tion Utilities mode, see
Controller
fails to start on page
361.
Install/re-install RobotWare, if pos-
sible.
The main computer may be faulty,
replace it and verify that the fault
has been fixed.
© Copyright 2022-2023 ABB. All rights reserved.
Note
Verify that the input to A2.K1.X1 is 25.2 VDC
+/- 5%.
If the measured voltage is normal, pro-
ceed with step 13.
If the measured voltage is abnormal,
proceed with step 7.
If the connection and cables seem OK, proceed
with step 8.
Verify that the input to A1.X6 is 25.2 VDC +/-
5%.
If the measured voltage is normal, pro-
ceed with step 9.
If the measured voltage is abnormal,
troubleshoot the power unit. See
Troubleshooting the power unit on
page
381.
If the UPS LED is:
Steady green: Proceed with step 11.
Off: Proceed with step 10.
If the error message is insufficient, pro-
ceed with step 11.
If an error was resolved, restart from
step 4.
See
Replacing the main computer on page
Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
231.