7 Troubleshooting
7.2.1 No LEDs are lit on the controller
Continued
Detailed working procedure
1
2
3
4
5
6
7
8
348
Action
Make sure that the mains switch (Q0) has been
switched on.
Make sure that the system is supplied with power.
Measure incoming mains voltage and make
sure the voltage is within the normal range.
Check that the mains connection (X0) is properly
connected.
Tip
For more details, see Circuit diagram - OmniCore
V400XT.
Check that the AC input cable is properly connec-
ted.
Check the output voltage of (Q0).
Make sure that (Q0) is closed.
Check the fuse (F1).
Check connector A1.X1.
Check the LED status.
© Copyright 2022-2023 ABB. All rights reserved.
Note
Use a multimeter and insulating
gloves.
If incoming mains is not ok, the
problem is not in the robot control-
ler. Troubleshoot incoming mains.
Use a multimeter and insulating
gloves.
Replace if damaged.
If abnormal, troubleshoot
the power unit. See
Troubleshooting the power
unit on page
381.
If abnormal, troubleshoot
the LEDs. See
Troubleshooting LEDs in the
controller on page
Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
366.