7.2.5 Problem starting or connecting the FlexPendant
Action
Check that the FlexPendant cable is correctly
connected to the controller through the HMI signal
connector, X4.
Check the FlexPendant cable for any damage.
If possible, test by connecting another FlexPend-
ant. This is to eliminate the FlexPendant and cable
as error sources; Test the FlexPendant with a
different controller to eliminate the controller as
error source.
Check that the FlexPendant works normally.
Tip
This is detailed in section
FlexPendant on page
367.
© Copyright 2022-2023 ABB. All rights reserved.
Note
If it is not connected, repair the
connection and go to step six.
Check the pins in the connector.
If it is ok, go to the next step.
If it is not ok, contact your local
ABB.
Troubleshooting the
7 Troubleshooting
Continued
If damage is found, replace
the FlexPendant cable and
go to step six.
If it is ok, go to the next
step.