Inform the system administrator of any suspected bad devices found in this step.
Replace or remove any bad devices.
9. If the device is present, then perform a health check.
See "Perform Health Check" on page 131.
10. Review the host event log.
11. See "Check the Host Event Log" on page 131.
12. If SCSI errors are found, then inform the system administrator that the connected
device appears to be bad. Replace or remove any bad devices.
13. After all possible device checks are performed go to "Restore SCSI Setup" below.

Restore SCSI Setup

1. Perform a graceful shutdown of the Scalar 100.
2. Reconnect all available SCSI devices to their proper channel assignments (either their
original configuration, or with any changes made per this MAP).
3. Wait for the SNC and the Scalar 100 to finish booting. The Scalar 100 takes longer to
boot than the SNC does.
4. If the SNC is in diagnostic mode (command prompt = diagmode >), then restore
normal operation.
See "Restoring Normal Mode" on page 248.
5. Perform a health check.
See "Perform Health Check" on page 131.
6. Review the host event log.
See "Check Event Log" on page 130.
7. If all attached SCSI devices and cables are determined to be good, yet SCSI errors
persist, then replace the SNC.
Go to "Removing the SNC" on page 155.
8. Exit this MAP.