Digi IX10 User Manual page 228

Hide thumbs Also See for IX10:
Table of Contents

Advertisement

Serial port
c. Parity: For Parity, select the type of parity used by the device to which you want to
connect. The default is None.
d. Stop bits: For Stop bits, select the number of stop bits used by the device to which you
want to connect. The default is 1.
e. Flow control: For Flow control, select the type of flow control used by the device to
which you want to connect. The default is None.
8. Click Apply to save the configuration and apply the change.
  Command line
1. Select the device in Remote Manager and click Actions > Open Console, or log into the IX10
local command line as a user with full Admin access rights.
Depending on your device configuration, you may be presented with an Access selection
menu. Type admin to access the Admin CLI.
2. At the command line, type config to enter configuration mode:
> config
(config)>
3. The serial port is enabled by default. To disable:
(config)> serial port1 enable false
(config)>
4. Set the mode:
(config)> serial port1 mode modbus
(config)>
5. Set the signaling interface type used on this serial port:
rs-232
n
rs-485
n
l
The default is rs-232.
6. (Optional) Set a label that will be used when referring to this port.
(config)>path-paramlabel label
(config)>
7. 1. Set the baud rate used by the device to which you want to connect:
(config)>serial port1 baudrate rate
(config)>
IX10 User Guide
Enable termination if you want to enable electrical termination on this serial port:
(config)> serial port1 termination true
(config)>
Configure Modbus mode
228

Advertisement

Table of Contents
loading