TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
... 8 Electrical connections
... Electrical data for inputs and outputs
Output – HART®
Note
The HART® protocol is an unsecured protocol, as such the
intended application should be assessed to ensure that these
protocols are suitable before implementation.
Transmission behavior
Temperature linear
Resistance linear
Voltage linear
Output signal
Configurable 4 to 20 mA (standard)
Configurable 20 to 4 mA
(dynamic range:3.8 to 20.5 mA in accordance with NE 43)
Simulation mode
3.5 to 23.6 mA
Induced current consumption
< 3.5 mA
Maximum output current
23.6 mA
Configurable error current signal
Note
Regardless of the alarm setting (underrange or overrange), a
high alarm or low alarm is always generated for some internal
device errors (e.g. hardware errors). Detailed information about
this can be found in the SIL-Safety Manual.
Notice – Before SW-Rev.: 03.00
The default factory setting for the error current signal is high
alarm 22 mA.
Overrange / high alarm 22 mA (20.0 to 23.6 mA)
Underrange / low alarm 3.6 mA (3.5 to 4.0 mA)
Notice – From SW-Rev.: 03.00
The default factory setting for the error current signal is low
alarm 3.5 mA, in accordance with NAMUR recommendations
NE 93, NE 107 and NE 131.
Overrange / high alarm 22 mA (20.0 to 23.6 mA)
Underrange / low alarm 3.5 mA (3.5 to 4.0 mA)
Output – PROFIBUS PA®
Note
The PROFIBUS PA® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
these protocols are suitable before implementation.
Output signal
PROFIBUS – MBP (IEC 61158-2)
Baud rate 31.25 kBit/s
PA-Profile 3.01
FISCO compliant (IEC 60079-27)
ID-Number: 0x3470 [0x9700]
Error current signal
FDE (Fault Disconnection Electronic)
Block structure
Physical Block
Transducer Block 1 – Temperature
Transducer Block 2 – HMI (LCD indicator)
Transducer Block 3 – enhanced diagnosis
Analog Input 1 – Primary Value (Calculated Value*
Analog Input 2 – SECONDARY VALUE_1 (Sensor 1)
Analog Input 3 – SECONDARY VALUE_2 (Sensor 2)
Analog Input 4 – SECONDARY VALUE_3 (reference junction
temperature)
Analog Output – optional HMI display
(Transducer Block 2)
Discrete Input 1 – extended diagnosis 1
(Transducer Block 3)
Discrete Input 2 – extended diagnosis 2
(Transducer Block 3)
*
Sensor 1, Sensor 2 or difference or mean
For detailed information see the PROFIBUS PA® interface
description (COM/TTX300/PB).
)