Set the Current Output limits
When the Current Output limits on alarm and saturation different from the selected is needed it is possible to
change it following one of the methods described in the next paragraphs.
Set the Current Output limits on the Digital LCD Integral Display
To set High Saturation current
Navigate the Digital LCD Integral Display menu, select
High Saturation
> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the High saturation current: 2 – 4 – 2 – 1 – Edit
To set Low Saturation current
Navigate the Digital LCD Integral Display menu, select
Low
Saturation> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Low saturation current: 2 – 4 – 2 – 2 – Edit
To set Fail High current
Navigate the Digital LCD Integral Display menu, select
Fail
High> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Fail High current: 2 – 4 – 2 – 3 - Edit
To set Fail Low current
Navigate the Digital LCD Integral Display menu, select
Fail
Low> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Fail Low current: 2 – 4 – 2 – 4 - Edit
Set the Current Output limits by HHT
The setting of the Current Output limits by Hand Held Terminal is availa ble. Please refer to the device
manual for the right operations.
Set the Current Output limits by PC
The setting of the Current Output limits by PC is available using dedicated Software. ABB can provide the
references and the Software. Please refer to the Software instructions for the right operations.
364Ax-Gx Instruction Manual
Device config
>
Output on alarm
Device config
>
Output on alarm
Device config
>
Output on alarm
Device config
>
Output on alarm
>
Set Fail Current
>
>
Set Fail Current
>
>
>
Set Fail Current
>
Set Fail Current
>
32