Remote Meter wiring

Before starting the Re mote Meter wi ring be sure that the transmitter h as been wi red according t o the
previous paragraph instructions.
Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. High voltage
Follow these steps to wire the Remote Meter:
1. Remove the housing cover.
In an Explosion-Proof/Flame-Proof installation, do not remove the transmitter covers when power is applied
to the unit. Remove the power supply first and continue the operation
2. Run wiring through the same port of the electrical connection or the other port removing the plug.
3. Connect the positive lead of the remote meter to the "EXT METER +" terminal, and the negative lead to
the "–" terminal.
4. Plug and seal the ports. Make sure that when the installation has been completed, the ports are properly
sealed against entry of water and corrosive vapors and gases.
Cables, cable gland and unused port plug must be in accordance with the intended type of protection (e.g.
intrinsically safe, explosion proof, etc.) and degree of protection (e.g. IP6x or NEMA 4x). In particular, for
explosion proof installation, plug the unused opening with a plug certified for explosion containment.
WARNING !
that may be present on leads can cause electrical shock.
WARNING !
WARNING !
364Ax-Gx Instruction Manual