Operating Instruction OI/TTR200-EN Rev. B
TTR200
Rail-mount temperature transmitter
Measurement made easy

Advertisement

Table of Contents
loading

Summary of Contents for ABB ttr200

  • Page 1 Operating Instruction OI/TTR200-EN Rev. B TTR200 Rail-mount temperature transmitter Measurement made easy...
  • Page 2 Short product description Rail-mount temperature transmitter for the measurement of the temperature of liquid and gaseous measuring media. Further Information Additional documentation on TTR200 is available free of charge for downloading at www.abb.com/temperature. Alternatively, scan this code: Manufacturer ABB Automation Products GmbH Process Automation Schillerstr.
  • Page 3: Table Of Contents

    Electrical connections ........11     7.2.1 Conductor material ..........11     7.2.2 Pin configuration ..........12     7.2.3 Electrical data for inputs and outputs ....13     Power supply ............. 14 TTR200 | OI/TTR200-EN Rev. B 3...
  • Page 4: Safety

    The signal word "NOTICE" indicates useful or important information about the product. The signal word "NOTICE" is not a signal word indicating a danger to personnel. The signal word "NOTICE" can also refer to material damage. 4 OI/TTR200-EN Rev. B | TTR200...
  • Page 5: Use In Potentially Explosive Atmospheres According To Atex And Iecex

    = 1.05 μF external capacitance 1) From HW rev. 1.12, previously I = 25 mA. 2) From HW rev. 1.12, previously P = 38 mW. 3) From HW rev. 1.12, previously C = 49 nF. TTR200 | OI/TTR200-EN Rev. B 5...
  • Page 6: Installation Instructions

    (observe the warnings on the device). ≥ As the user, it is your responsibility to ensure that the sensor ≥ instrumentation meets the requirements of applicable ≥ explosion protection standards. (cable) ≤ (cable) ≤ 6 OI/TTR200-EN Rev. B | TTR200...
  • Page 7: Commissioning

    As the user, it is your responsibility to ensure that the sensor instrumentation meets the requirements of applicable explosion protection standards. The sensor can be installed in Zone 0, Zone 1, or Zone 20. TTR200 | OI/TTR200-EN Rev. B 7...
  • Page 8: Use In Potentially Explosive Atmospheres In Accordance With Fm And Csa

    Class I, Zone 0, Ex ia Group IIC T6 out in relation to the limit values of the equipment: CSA Non-Incendive Model TTR200-R6 Control Drawing TTR200-R6H (N.I.) Class I, Div. 2, Groups A, B, C, D 8 OI/TTR200-EN Rev. B | TTR200...
  • Page 9: Commissioning

    Function and system design Transmitters Supply isolator / DCS input (intrinsically safe equipment) (related equipment) TTR200 digital transmitters are communication-ready devices ≥ with microprocessor-controlled electronics. It corresponds to ≥ the housing IP rating IP 20 and is suited for 35 mm rail ≥...
  • Page 10: Product Identification

    (optional) j Software version number k Hardware version number l Sensor configuration m Supply voltage range, typical current range, log n Serial number o Order number p Ordering number 10 OI/TTR200-EN Rev. B | TTR200...
  • Page 11: Installation

    — Safe isolation of electrical circuits which are dangerous if touched is only guaranteed if the connected devices satisfy the requirements of DIN EN 61140 (VDE 0140 Part 1) (basic requirements for safe isolation). Change from two to one column TTR200 | OI/TTR200-EN Rev. B 11...
  • Page 12: Pin Configuration

    — ERR / red LED: sensor, sensor lead & unit fault signaling — DIP switch 1: on -> hardware write protection enabled — DIP switch 2: without function Change from one to two columns 12 OI/TTR200-EN Rev. B | TTR200...
  • Page 13: Electrical Data For Inputs And Outputs

    Simulation mode 3.5 ... 23.6 mA Induced current consumption < 3.5 mA Maximum output current 23.6 mA Configurable error current signal — Overrange 22 mA (20.0 … 23.6 mA) — Underrange 3.6 mA (3.5 … 4.0 mA) TTR200 | OI/TTR200-EN Rev. B 13...
  • Page 14: Power Supply

    Fig. 10: Maximum load depending on input terminal voltage A TTR200 B TTR200 in Ex ia design C HART communication resistance Maximum power consumption — P = U x 0.022 A...
  • Page 15: Commissioning

    On: Local write protection activated — With EDD 2 Without function Configuration can be performed within an EDD frame application that is approved for use with the EDD. NOTICE —Factory settings: Both switches "OFF". Local write protection deactivated TTR200 | OI/TTR200-EN Rev. B 15...
  • Page 16: Configuration Types

    — FDT / DTM technology – via TTX200-DTM driver calibration. — EDD - via TTX200 EDD driver Diagnostic message — Overrange / underrange in accordance with NE 43 — HART diagnosis 16 OI/TTR200-EN Rev. B | TTR200...
  • Page 17: D/A Analog Output Adjustment (4 And 20 Ma Trim)17

    4 … 20 mA output signal and the digital HART signal now match. The adjustment should be repeated when connecting the transmitter to another input of a higher-level system. Change from two to one column TTR200 | OI/TTR200-EN Rev. B 17...
  • Page 18: Parameter Descriptions

    — Three-wire: sensor connection type in three-wire technology — Four-wire: sensor connection type in four-wire technology <Sensor / Line resistance> Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit Value range: 0 ... 100 Ω 18 OI/TTR200-EN Rev. B | TTR200...
  • Page 19: Factory Settings

    Write protection Input Sensor Type Pt100 (IEC60751) R-Connection Three-wire circuit Measured Range Begin Measured Range End Engineering Unit Degrees C Damping Process Alarm Fault signaling Overrange 22 mA Change from one to two columns TTR200 | OI/TTR200-EN Rev. B 19...
  • Page 20: Diagnosis / Error Messages

    10.2 Analog output / LED diagnostic information No on-site repair or replacement of electronic parts is planned. The TTR200 features a green and a red diagnostic LED for fault signaling. 11.1 Cleaning The green LED indicates that the supply voltage is connected...
  • Page 21: Recycling And Disposal

    — If it is not possible to dispose of old equipment properly, 16 Declaration of conformity ABB Service can take receipt of and dispose of returns for a fee. NOTICE 13.2 Information on ROHS Directive 2011/65/EC...
  • Page 22: Appendix

    Which substances have come into contact with the device? We hereby state that the devices / components shipped have been cleaned and are free from any dangerous or poisonous substances. Town/city, date Signature and company stamp 22 OI/TTR200-EN Rev. B | TTR200...
  • Page 23 Notes Notes TTR200 | OI/TTR200-EN Rev. B 23...
  • Page 24 Howard Road, St. Neots notice. Cambridgeshire, PE19 8EU With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or Tel: +44 (0)870 600 6122 possible lack of information in this document.

This manual is also suitable for:

Tth200