Temperature Data; Transmitter; Lcd Indicator; Electrical Data - ABB TTF300 Operating Instruction

Field-mount temperature transmitter
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

8
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
... 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx

Temperature data

Transmitter

ATEX / IECEx intrinsic safety, ATEX increased safety as well
as dust explosion protection (Zone 22)
Temperature class
T6, T5
T4 to T1
ATEX / IECEx flameproof (enclosure)
Temperature class
Permissible ambient temperature range on the
T6
T4 to T1

LCD indicator

ATEX / IECEx intrinsic safety
Temperature class
T6
T4 to T1
Permissible ambient temperature range
−50 to 56 °C
(−58 to 132.8 °F)
−50 to 85 °C
(−58 to 185.0 °F)
connection head
−40 to 67 °C
(−40 to 152 °F)
−40 to 85 °C
(−40 to 185 °F)
Permissible ambient temperature range
−50 to 56 °C
(−58 to 132.8 °F)
−50 to 85 °C
(−58 to 185 °F)

Electrical data

Transmitter
Intrinsic safety type of protection Ex ia IIC (Part 1)
Supply circuit
TTF300-E1H
TTF300-H1H
Max. voltage
Short-circuit current
Max. power
Internal inductance
L
i
Internal capacitance
C
= 0.57 nF***
i
*
II B FISCO: I
≤ 380 mA, P
≤ 5.32 W
i
i
**
Only applies to HART variant. From HW-Rev.: 02.00, previously 0.5 mH
*** Only applies for HART variants. From HW-Rev.: 1.07, previously 5 nF
Intrinsic safety type of protection Ex ia IIC (Part 2)
TTF300-E1H, TTF300-H1H measurement current circuit model
thermometers, resistors
Max. voltage
Short-circuit current
Max. power
Internal inductance
Internal capacitance
Maximum permissible
external inductance
Maximum permissible
external capacitance
1
From HW-Rev.: 02.00, previously 25 mA
2
From HW-Rev.: 02.00, previously 38 mW
3
From HW-Rev.: 02.00, previously 1.55 μF
4
From HW-Rev.: 02.00, previously 1.05 μF
TTF300-E1P/-H1P
TTF300-E1F/-H1F
FISCO*
U
= 30 V
U
≤ 17.5 V
i
i
I
= 130 mA
I
≤ 183 mA*
i
i
P
= 0.8 W
P
≤ 2.56 W*
i
i
= 160 μH**
L
≤ 10 μH
i
C
≤ 5 nF
i
Resistance
Thermocouples, voltages
U
= 6.5 V
o
I
= 17.8 mA
1
o
P
= 29 mW
2
o
L
≈ 0 mH
i
(negligible)
C
= 49 nF
i
L
= 5 mH
o
C
= 1.65 μF
3
o
ENTITY
U
≤ 24.0 V
i
I
≤ 250 mA
i
P
≤ 1.2 W
i
L
≤ 10 μH
i
C
≤ 5 nF
i
U
= 1.2 V
o
I
= 50 mA
o
P
= 60 mW
o
L
≈ 0 mH
i
(negligible)
C
= 49 nF
i
L
= 5 mH
o
C
= 1.15 μF
4
o

Advertisement

Table of Contents
loading

Table of Contents