Goodrive300-19 series open loop vector inverter special for hosit
Function
Name
code
DEC time
Jumping
P08.09
frequency 1
Jumping
P08.10
frequency
range 1
Jumping
P08.11
frequency 2
Jumping
P08.12
frequency
range 2
Jumping
P08.13
frequency 3
Jumping
P08.14
frequency
range 3
Set running
P08.27
time
Fault reset
P08.28
times
Interval time
P08.29
of automatic
fault reset
Frequency
P08.30
decreasing
Detailed instruction of parameters
Setting range: 0.0~3600.0s
When the set frequency is in the range of jumping
frequency, the inverter will run at the edge of the
jumping frequency.
The inverter can avoid the mechanical resonance
point by setting the jumping frequency. The inverter
can set three jumping frequency. But this function will
be invalid if all jumping points are 0.
Setting range: 0.00Hz~P00.03 (the Max. frequency)
Pre-set running time of the inverter. When the
accumulative running time achieves the set time, the
multi-function digital output terminals will output the
signal of "running time arrival".
Setting range: 0~65535min
Fault reset times: set the automatic fault reset times.
If the reset time exceeds this set value, the inverter
will stop to wait maintenance.
Interval time of automatic fault reset: the interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~3600.0s
The output frequency of the inverter changes as the
load. And it is mainly used to balance the power when
-92-
Function parameters
Default
Modify
value
on
model
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0min
○
0
○
1.0s
○
0.00Hz