Goodrive300-19 series open loop vector inverter special for hosit
Code
protection
IGBT W phase
OUt3
protection
Accelerating
OV1
overvoltage
Decelerating
OV2
overvoltage
Constant
OV3
overvoltage
Accelerating
OC1
overcurrent
Decelerating
OC2
overcurrent
Constant
OC3
overcurrent
Bus undervoltage
UV
OL1
Motor overload
Fault
phase;
Interference causes faulty
action;
The connection of the
driving wires is not good;
The grounding is not good
1. The input voltage is
abnormal.
2. There is large energy
feedback.
3. No braking components.
4. Braking energy is not
open
1. The acceleration or
deceleration is too fast.
2. The voltage of the grid is
too low.
3. The power of the inverter
is too low.
4. The load transients or is
abnormal.
5. The grounding is short
circuited or the output is
phase loss.
6. There is strong external
interference.
7. The overvoltage stall
protection is not open.
1. The voltage of the power
supply is too low.
fault
2. The overvoltage stall
protection is not open.
The voltage of the power
Cause
-191-
Fault tracking
Solution
Check if there is strong
interference to the external
equipment
1. Check the input power
2. Check if the DEC time of
the load is too short or the
inverter starts during the
rotation of the motor or it
needs to increase the energy
consumption components.
3. Install the braking
components.
4. Check the setting of
relative function codes.
1. Increase the ACC time
2. Check the input power
3. Select the inverter with a
larger power
4. Check if the load is short
circuited (the grounding short
circuited or the wire short
circuited) or the rotation is not
smooth.
5. Check the output
configuration.
6. Check if there is strong
interference.
7. Check the setting of
relative function codes.
1. Check the input power of
the supply line.
2. Check the setting of
relative function codes.
Check the power of the