Function
Name
code
AI3
Upper limit of
P05.46
AI3
Correspondin
g setting of
P05.47
the upper
limit of AI3
AI3 input filter
P05.48
time
HDI
high-speed
P05.49
pulse input
function
selection
Lower limit
P05.50
frequency of
HDI
Correspondin
g setting of
P05.51
HDI lower
limit
frequency
Upper limit
P05.52
frequency of
HDI
Correspondin
g setting of
P05.53
HDI upper
limit
frequency
HDI
P05.54
frequency
input filter
Detailed instruction of parameters
The setting range of P05.44: P05.42~P05.46
The setting range of P05.45: -100.0%~100.0%
The setting range of P05.46: P05.44~10.00V
The setting range of P05.47: -100.0%~100.0%
The setting range of P05.48: 0.000s~10.000s
The function selection when HDI terminals is
high-speed pulse input
0: Frequency setting input, frequency setting source
1~2: Reserved
0.00 kHz~P05.52
-100.0%~100.0%
P05.50~50.00kHz
-100.0%~100.0%
0.000s~10.000s
-77-
Function parameters
Default
Modify
value
10.00V
100.0%
0.100s
0
0.00kHz
0.0%
50.00kHz
100.0%
0. 010s