Goodrive300-19 series open loop vector inverter special for hosit
Function
Name
code
feedback
detection time
Contactor
P19.25
feedback
detection time
Detection
time of torque
P19.26
verification
fault
Detection
enabling at
P19.27
joystick zero
position
Delay time at
P19.28
joystick zero
position
Light load
P19.29
acceleration
enabling
P19.30
Reserved
Torque
P19.31
detection
value at FWD
Detailed instruction of parameters
detailed instruction of parameters
Setting range: 0.00~20.000s
0.00~20.000s
When the set values of torque verification current and
torque are non-zero, torque verification function is
valid. During running, if the output torque or current is
smaller than the set value and the hold time is larger
than P19.26, the inverter will stop because of torque
verification fault and the keypad will display TPF.
Setting range: 0.00~10.000s
The function codes are used for detection functions at
joystick zero position
When P19.27=1, detection enabling at joystick zero
position is valid. After the inverter stops, to avoid
restart of the inverter, make sure the joystick returns
to zero position (neutral position). The inverter can
restart only when the joystick returns to zero position
and the time is larger than P19.28.
Note: Signals at zero position are valid only under
joystick mode and hierarchical joystick mode.
Setting range of P19.27:
0: Disabled
1: Enabled
Setting range of P19.28: 0.000~60.000s
0: Disabled
1: Enabled
0.0~150.0%
-115-
Function parameters
Default
Modify
value
1.000s
0.500s
0
0.300s
0
60.0%