Goodrive300-19 series open loop vector inverter special for hosit
Function
Name
code
at sudden
power loss
Frequency
decreasing
P11.02
ratio at
sudden
power loss
Overvoltage
P11.03
stall
protection
Voltage
protection of
P11.04
overvoltage
stall
P11.05
Current limit The actual increasing ratio of motor speed is lower
Detailed instruction of parameters
Setting range: 0.00Hz/s~P00.03 (the Max. frequency)
After the power loss of the grid, the bus voltage drops
to the sudden frequency decreasing point, the
inverter begins to decrease the running frequency at
P11.02 to make the inverter generate power again.
The returning power can maintain the bus voltage to
ensure a rated running of the inverter until the
recovery of power.
Voltage degree
Frequency
decreasing
threshold
Note:
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during the
switching of the grid.
2. Prohibition of input phase loss protection can
enable this function.
0: Disable
1: Enable
120~150% (standard bus voltage) (380V)
220V
380V
660V
260V
460V
800V
-100-
Function parameters
Default
Modify
value
○
10.00Hz/s
○
1
○
136%
◎
01