Goodrive300-19 series open loop vector inverter special for hosit
Function
Name
code
parameter
autotuning
AVR
P00.16
function
selection
Function
P00.18
restore
parameter
P01 Group Start-up and stop control
P01.00
Start mode
Detailed instruction of parameters
1: Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when
high control accuracy is needed.
2: Static autotuning 1 (autotune totally); It is suitable
in the cases when the motor cannot de-couple from
the load.
3: Static autotuning 2 (autotune partially); when the
current motor is motor 1, autotune P02.06, P02.07,
P02.08; and when the current motor is motor 2,
autotune P12.06, P12.07, P12.08.
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the inverter can cancel
the impact on the output voltage of the inverter
because of the bus voltage fluctuation.
0: No operation
1: Restore the default value
2: Cancel the fault record
Note: The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0: Start-up directly: start from the starting frequency
P01.01.
1: Start-up after DC braking: start the motor from the
starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in the
cases where reverse rotation may occur to the low
inertia load during starting.
2: Start-up after speed tracing: start the rotating motor
-50-
Function parameters
Default
Modify
value
○
1
◎
0
◎
0
Need help?
Do you have a question about the Goodrive300-19 Series and is the answer not in the manual?
Questions and answers