4 Operation

4.8.4 Confirming Safety Functions

(3) Procedure
4.8.4

Confirming Safety Functions

When starting the equipment or replacing the SERVOPACK or converter for maintenance, be sure to conduct
the following confirmation test on the HWBB function after wiring.
• When the /HWBB1 and /HWBB2 signals turn OFF, check that the digital operator displays "Hbb" and that
the servomotor does not operate.
• Check the ON/OFF states of the /HWBB1 and /HWBB2 signals with Un015.
→ If the ON/OFF states of the signals do not coincide with the display, an error in the external device, dis-
connection or short-circuiting of the external wiring, or a failure in the SERVOPACK or converter must be
considered. Find the cause and correct the problem.
• Check with the display of the feedback circuit input of the connected device to confirm that the EDM1 sig-
nal is OFF while in normal operation.
4.8.5

Connecting a Safety Function Device

There are two types of the safety function's jumper connectors that are attached to SERVOPACKs. You must
remove a safety function's jumper connector before connecting a safety function device. The connection
method depends on the connector type that is used. Read the following procedures well before you attach a
safety function device.
Use the following procedures to attach safety function devices.
4-64
1
Request to open the guard.
When the servomotor is operating, the host
controller stops the servomotor and sends
2
the servo OFF command (SV_OFF).
3
Open the guard and enter.
The /HWBB1 and /HWBB2 signals are
4
OFF and HWBB function operates.
(The operation in the guard is available.)
After completing the operation, leave and
5
close the guard.
The host controller sends the servo ON com-
6
mand (SV_ON).
Connector Type A
Connector Type B